<B1. Engineering>

B1-36

IM 01W01F01-01EN

B1.3.1.3 Monitoring Field Wireless Device Status

A device patrol function of PRM can be used to monitor the status of field wireless devices.
For details on the device patrol function and the setup procedure, refer to the user's manuals of

PRM.
A field wireless device that supports ISA100.11a field wireless communication monitors the de-

vice status using the following parameter to perform device patrol.

Parameter name

: DIAG_STATUS

Data type

: Unsigned32

Address

: TSAP ID = 2, Object ID = 1, Attribute ID = 67

Table B1-15 Content of DIAG_STATUS

Bit

Description

Bit31(MSB)

F: Failure status

Bit30

C: Function check status

Bit29

O: Out of specification status

Bit28

M: Maintenance required status

Bit27

Faults in electronics

Bit26

Faults in sensor or actuator element

Bit25

Installation, calibration problem

Bit24

Out of service

Bit23

Outside sensor limits

Bit22

Environmental conditions out of device specification

Bit21

Fault prediction: Maintenance required

Bit20

Power is critical low: maintenance need short-term

Bit19

Power is low: maintenance need mid-term

Bit18

Software update incomplete

Bit17

Simulation is active

Bit16-Bit8

reserved for Baseline Device Profile

Bit7-Bit01

vendor specific area

Bit00

Detail information available

1: available

0: no available