C2-15 – Yokogawa YFGW710 User Manual

Page 136

Advertising
background image

<C2. Field Wireless Configurator>

C2-15

IM 01W01F01-01EN

2) Loading provisioning information file
Load provisioning information (EUI-64, join key, etc.) from the provisioning information file as fol-

lows.
1. Click the toolbar button on the Device tab page.
2. Specify the provisioning information file to be loaded, and click [Open].
3. When loading the provisioning information:

• If a file with the same Device Tag and Network ID already exists in the project, the Device

Provisioning window will prompt you to select the devices that you wish to update. Push

[OK] to execute loading, the EUI-64 and Join Key of the selected devices will be updated.

(Figure C2-14)

• If files with different Device Tags and Network IDs has the same EUI-64, or the same EUI-64

exists in the projects with different Device Tags, the whole import process will be stopped

and an error message will be shown.

• If no duplicate devices exist, a new device entry is created in the project for that device.
• A popup window is displayed, informing the number of entries created/renewed registered.
• If the project database contains Network IDs with the same EUI-64, but with different device

tags or network IDs, the provisioning information will not be imported for the device. The

device tag of the device and the items that differ appear in the pane shown below.

4. After reading the provisioning information, read the CF file and complete the settings of

devices.