B2.2 troubleshooting and recovery task, B2.2, B2-2 – Yokogawa YFGW710 User Manual

Page 113

Advertising
background image

<B2. System Maintenance>

B2-2

IM 01W01F01-01EN

B2.2 Troubleshooting and Recovery Task

This section describes the troubleshooting and recovery procedure for the process alarms and

system alarms that are displayed in the control system and the device alarms that are displayed

in PRM.
Field Wireless Management Tool is used for the troubleshooting.

Process alarm generation

FWMT: Field Wireless Management Tool
GW: YFGW710
BBR : Backbone Router
SM : System Manager

Can GW

be accessed

from FWMT?

Is the

system alarm of

the device occurring

simultaneously?

Is the

remaining battery

power of the device

enough?

Is the

system alarm

indicating

a GW failure occurring

simultaneously?

Is

system alarm

occurring for

all devices existing on the

same network

simultaneously?

Can GW be

accessed

from FWMT?

Is one

or more

devices

joining the field

wireless network

displayed in FWMT?

(With exception of

GW/BBR/SM)

Field wireless network
conditions
are considered to be unstable.
Consult with Yokogawa

There is the possibility of

a routing error

between the control

system and GW.

Check the route for

broken wire, HUB failure,

etc.

There is the possibility of

a routing error between

FWMT and GW. Check

the route for broken wire,

HUB failure, etc.

There is the possibility of
a gateway failure.
Replace the gateway.

There is the possibility of
a gateway failure.
Replace the gateway.

Device failure. Contact
the device vendor.

Replace the batteries.

Process error. Check
the upper and lower
limit of the process
data, etc.

YES

NO

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Note 1

Note 2

Note 4

Note 3

Note 5

Note 6

FB0201.ai

Figure B2-1 Troubleshooting and Recovery Procedure