B1-30 – Yokogawa YFGW710 User Manual

Page 94

Advertising
background image

<B1. Engineering>

B1-30

IM 01W01F01-01EN

l

Device tags do not match

When downloading the process data communication definitions to the device from Field Wire-

less Configurator and the device tag registered with the project database and the device tag set

to the device by provisioning do not match, the following message appears and the download is

stopped.

<Device tag 1> Device Tag is not correct! <Device tag 2> is assigned

Device tag 1: Device tag registered with the project data base
Device tag 2: Device tag actually set to the device

In this case, either change the device tag in the project database, or perform the provisioning

task again and set the device tag to the field wireless device again. Note that when provisioning

is performed again, the provisioning information needs to be registered with the project database

and written to YFGW710 again.

l

CFs do not match

When the CF used by the field wireless network offline engineering does not match the CF of the

target device, a download error occurs.
Check whether or not the CF used is correct using the following procedure.

• In the [Download Project Data] window shown in Figure B1-7, place a check in the checkbox

for [Verify vendor and model before downloading device].

• Performing download

When a check is placed in the checkbox for [Verify vendor and model before downloading de-

vice], Field Wireless Configurator obtains the vendor ID and model ID in IDENT_NUMBER of

the device and compares them with the vendor ID and model ID in CF before downloading the

process data communication definitions. When the vendor IDs and model IDs do not match, the

following message appears and the download is stopped.

<Device tag> IDENT_NUMBER is not correct! VendorID=0x00594543, ModelID=0x000C,

DeviceRev=1

Device tag: Device tag registered with the project database
Vendor ID: Device vendor (0x00594543 for Yokogawa)
Model ID: Device model (0x000C for EJX)

In this case, inform the device vendor about the vendor ID, model ID, and device revision, and

obtain CF that matches the device information. After obtaining CF, replace the existing CF with

a new CF using Field Wireless Configurator, and define the process data communication again.

Define the Modbus Register map again if necessary.

l

For the case that you find the following message when the timeout occurs

after starting the download without a marking “Verify vendor and model before

downloading to device” checkbox in the [Download Project Data] window:

DEV001 download failed due to EUI64 write ObjectAttributeIndexAndSize Array configured NG

due to timeout!! (Ex. Device TAG: DEV001)
When the above message appears during the download, wait for three minutes, and then per-

form the download to the target device again using Field Wireless Configurator.

l

For the case that you find the following message when the timeout occurs

after starting the download with a marking “Verify vendor and model before

downloading to device” checkbox in the [Download Project Data] window, de-

pending on the timing of the downloading of Field Wireless Configurator or the

timing of the device provisioning to the wireless network:

Advertising