<A3. YFGW710 Field Wireless Integrated Gateway>

A3-37

IM 01W01F01-01EN

n

Optional Specifications(For Explosion Protected Types)

Item

Description

Code

Factory Mutual

(FM)

FM nonincendive approval

Applicable standard: FM3600, FM3611, FM3810, ANSI/NEMA250

Nonincendive for Class I, Division 2, Groups A, B, C and D;

Class II, Division 2, Groups F and G;

Class III, Division 1 hazardous (Classified) locations.

Enclosure: NEMA 4X

Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)

FN17

ATEX

ATEX Type n declaration

Applicable standard: EN60079-0: 2009, EN60079-0: 2012,

EN60079-11: 2012, EN60079-15: 2010, EN60079-28: 2007

II 3G Ex nA [ic] [op is] IIC T4 Gc (with 100BASE-FX)

II 3G Ex nA [ic] IIC T4 Gc (without 100BASE-FX)

Enclosure: IP66

Amb. Temp.: –40 to 60°C (–40 to 140°F)

KN27

Canadian Standards

Association

(CSA)

CSA nonincendive approval

Certificate: 2342292

[For CSA C22.2]

Applicable standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25,

C22.2 No.94, C22.2 No.213, C22.2 No.61010-1-04

Nonincendive for Class I, Division 2, Groups A, B, C and D;

Class II, Division 2, Groups F and G;

Class III, Division 1

Enclosure: Type 4X

[For CSA E60079]

Applicable standard: CAN/CSA E60079-0, CAN/CSA E60079-15,

IEC60529

Ex nA nL IIC T4

Enclosure: IP66

Amb. Temp.: –40 to 60°C (–40 to 140°F)

CN17

IECEx Scheme

IECEx Type n approval

Certificate: IECEx DEK 13.0047

Applicable standard: IEC60079-0:2011, IEC60079-15:2010,

IEC 60079-11:2011

Ex nA [ic] IIC T4 Gc

Enclosure: IP66

Amb. Temp.: –40 to 60°C (–40 to 140°F)

SN27