C3.3.2.2.4 readings, C3-34 – Yokogawa YFGW710 User Manual

Page 188

Advertising
background image

<C3. Field Wireless Management Tool>

C3-34

IM 01W01F01-01EN

TIP

The firmware in field devices is updated wirelessly.
When an update operation is started on the gateway side, the field device initiates a Join operation.
Since the update operation must wait for up to about 30 minutes for the Join operation to complete, it is recom-

mended to start by updating the communication stack of a field device.
To update the sensor board firmware you first have to update the communication stack. Updating takes about 11

hours to complete.

C3.3.2.2.4 Readings

The Readings tab page allows you to view the last readings received from devices, which are

generated by automatic Publish/Subscribe commands. To access this page, select the Readings
option in the View menu or click the toolbar button .

Figure C 3-32

The readings can be filtered by the device tag. To search for readings, enter the device tag or part
of the tag in the Device Tag input field and click . The system will retrieve the last reading from

each attribute for all the devices whose tag contains the characters provided in the input field.
The results are displayed in a table that contains the following information for each reading:

• Device Tag
• Device EUI-64 address (Device unique 64bits address)
• Timestamp (date and time of reading),
• TSAP ID, Object ID, Attribute ID (ID of parameters' each layer structure)
• Status (The quality of the data being transmitted is indicated in hex format.)
• Data Type (Float, Unsigned32)

Advertising