<A3. YFGW710 Field Wireless Integrated Gateway>

A3-1

IM 01W01F01-01EN

A3. YFGW710 Field Wireless Integrated

Gateway

This chapter explains the installation of the YFGW710, antennas, cable connections, and mainte-

nance.

A3.1 Installation

A3.1.1 Requirements for Installation Locations

The installation of YFGW710 and field wireless devices must meet the following conditions:

• The field wireless equipment should be mounted in the place where no obstacle exists

around the antenna. Especially, YFGW710 should be mounted in the condition that no ob-

stacle exists around the antenna, in both cases of wall mounting and pipe mounting.

• If there is a pipe for mounting or plumbing in the direction except for the communication

partners, the antenna should be more than 30 cm apart from them.

• When the wall mounting does not satisfy the condition, use the extension cable to mount an

antenna in the place where there is no influence from any objects.

• All antennas must be in the upright position.
• The antenna of field wireless equipment must be installed at least 1.5 meter above the

ground (floor)

• The YFGW710 should be installed at a location as close as possible to the center of the field

wireless network.

• Ensure that the field wireless devices that are located within the wireless communication

range are within the line of sight of each other. In the star topology, the YFGW710 must

meet this condition.