<A3. YFGW710 Field Wireless Integrated Gateway>

A3-10

IM 01W01F01-01EN

l

Connection of Cable

The grounding terminals are located on the inside and outside of the terminal area.

Connect the cable to grounding terminal in accordance with wiring procedure 1) or 2).

1) Internal grounding terminal
If the power cable is a shielded cable, the shield

should be grounded at the terminal marked

as below.

2) External grounding terminal

M4 screw

(Bottom of the enclosure)

FA0308.ai

Fig. A 3-8 Wiring Procedure for Grounding Terminals

A3.2.3 Network Cable Connection

This section describes the connection of the optical and metal network cables.

IMPORTANT

According to the requirement of communication specification, select the optical Ethernet or the

metal Ethernet to communicate with the higher layer application.

A3.2.3.1 Optical Network Cable Connection

l

Applicable Cable

Table A 3-2 Specification of Optical Network Cable

Item

Specification

Optical Fiber Cable

Standard

100Base-FX

*1

Connector

SC Connector (1-pole x 2)

*2

Applicable Cable

Multi Mode Fiber (Central wavelength: 1300 nm)

50/125 um or 62.5/125 um

Inner tension must be nonmetals, such as FRP.

Transmission Range

2 km (Max.)

*1: 100Base-TX (Refer table A3-3) and 100Base-FX must be used exclusively.

*2: A double ferrule SC connector cannot be used. Be sure to use a single ferrule type.