A3-30 – Yokogawa YFGW710 User Manual

Page 50

Advertising
background image

<A3. YFGW710 Field Wireless Integrated Gateway>

A3-30

IM 01W01F01-01EN

• The thread type of the cable entries shall be confirmed according to the user’s manual.
• Cable glands, adapters and/or blanking elements shall be of type “n”, type “e” or type “d”

and shall be installed so as to maintain the specified degree of protection (IP code) of the

equipment.

• Keep the cap attached to the antenna connector (N type) until the installation of the antenna

or antenna cables to protect the inside of the connector from exposure of light. In case the

antenna or antenna cables are removed from the connector, the inside of the antenna con-

nector should be protected from exposure of light.

• The antenna and the surge arrester shall be a simple apparatus in accordance with

EN60079-11. Li and Ci of the simple apparatus shall be negligible. Temperature class of

them shall be determined from Po = 20 mW.

• The equipment shall be earthed in accordance with EN60079-14, in order to maintain in-

trinsic safety. A cable lug or a similar device shall be used to maintain the secureness of the

connection to the equipment. Care should be taken to avoid multi-point earthing since the

equipment is not galvanically isolated from the power supply.

• YFGW710 does not have a power switch inside. Prepare a dedicated breaker for the exter-

nal power line to turn ON/OFF the device.

• Make sure that the breakers are installed in the power supply circuits located in non-hazard-

ous areas so that the power can be shutoff when abnormality occurs.

• Note a warning label worded
“DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.”
“POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS.”
• Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the gen-

eration of electrostatic charge, such as rubbing with a dry cloth on coating face of product

and the antenna.

• Take care not to generate mechanical sparking when access to the instrument and periph-

eral devices in hazardous area.

Advertising