<B1. Engineering>

B1-17

IM 01W01F01-01EN

n

Procedure to Set YFGW710 Network Parameters

1. Connect the PC on which Field Wireless Configurator is installed to YFGW710 for which to

set the network parameters on a peer-to-peer basis.

2. To check the routing of the PC and YFGW710, access the current YFGW710

(192.168.0.101 by factory default) from the PC using the ping command. If the ping com-

mand does not work normally, a routing error occurs or there is a problem with the network

settings of the PC. Check the routing and the network settings of the PC.

3. Create a project using Field Wireless Configurator. This project is only used to change the

YFGW710 network parameters.

4. Set the values to change for IP Address, Subnet Mask, and Default Gateway in the [IPv4

Settings] field on the page of the [Network Information] tab in the Main window of Field Wire-

less Configurator. The other values do not need not to be changed. For the actual proce-

dure, refer to C2 of Part C of this document.

5. To set new YFGW710 network parameters, click on [Tools] – [Download] in the menu in the

Main window of Field Wireless Configurator to open the [Download Project Data] window.

6. Set the IP address before the change (192.168.0.101 for this example) for IP Address in the

[Connection Information] field in the [Download Project Data] window and click the [Start

download] button. After the download starts, YFGW710 will automatically restart during the

download. It will take a maximum of 2 minutes for YFGW710 to automatically restart and

then enter the running normally state.

7. When YFGW710 restarts, check that the new YFGW710 network parameters are set to

the target YFGW710 using the ping command from the PC. If the ping command response

is not normal, there is a problem with the network settings of the PC. In particular, when

the IP address was changed to a different segment (for example, when the IP address of

YFGW710 was changed from 192.168.0.101 to 10.0.1.1), the network settings of the PC

need to be set again so that access to the new segment becomes possible.