Device Commands

The Devices tab page allows users with appropriate roles to perform device-specific commands.

Commands include Rest Device, Get Channels Statistics, Read Object Attribute, and FW Com-

mands. Clicking on a device enables only the commands available for that device.
When you issue a command, the Command Results window opens indicating the command de-

tails: type, tracking number, parameters, date and time when the command was posted and the

response was received, status (which changes from New to Sent and then to Responded /Failed)

and response for that particular command. The command will also be listed in the Commands

Log.

l

Reset Device

This command is available for all registered network devices except for the System Manager,

and resets the firmware on that specific device.
To issue the command:
1) Select a device in the device list and then click on the [Reset Device] button.
2) At the Reset Device window, select the desired type of restart.

Figure C 3-23

Three types of resets can be performed on a device:

• Warm Restart: Resets firmware without changing the information set to the device.

The device will unregister and re-register

• Restart as provisioned: Clears set information while keeping only provisioning infor-

mation, and restarts the device. This command does not need to use for this system.

• Reset to Factory Defaults: Deletes set information and resets the device to shipment

settings. The device must be provisioned to join the network again. Gateway does not

support this command. This command does not need to use for this system.

3) Click [OK] to execute the command. The system will require confirmation in order to reset

the device. Click [OK] to perform the action or [Cancel] to abort.