C2.3.3.6 Error Checks

The Error Check option allows you to check for errors in the project data.
To perform error check;

Select Error Check in the Tools menu or click in the toolbar.
Upon downloading the network settings on YFGW710, check the “perform error check be-

fore downloading” option checkbox.

When error check starts, the Error Check section will open at the bottom of the project window,

and the Project Log section will automatically be selected (Figure C2-19).

Figure C 2-19

The Error Check window shows results containing the following items:

• Severity: Indicates the severity of the error (Information, Warning or Error)
• Network: Indicates ID of the network with the error
• Device: Indicates Device Tag of the device with the error
• Entity: Indicates the entity generated with the error
• Key: Indicates Join key of the specific device
• Details: Provides details of the error and possible correction tips

When OK is displayed at the end of the error check process, it means there is no error in the

project. Double-clicking on the error will open the place of the first error occurrence in the Project

Sections and Section Data areas. As the Error Check area remains open, you can detect error

occurrences easier and correct them swiftly.