C2-22, Ndevice replacement scenarios – Yokogawa YFGW710 User Manual
Page 143
<C2. Field Wireless Configurator>
C2-22
IM 01W01F01-01EN
l
Backbone Router
If you select the “Backbone Router” checkbox in the <Download Project Data> window, the fol-
lowing settings are sent to the YFGW710: “Device Tag,” “Filter Bit Mask,” and “Filter Target ID.”
The checkbox is selected by default if any of the values have changed since the last download
process. The “requires restart” status is always set.
After the settings are applied to the YFGW710 the restart command is sent to it (see IPv4 Set-
tings for more details on information generated upon YFGW710 restart).
l
Modbus Register Map and Pub/Sub Communication
If you select the “Modbus Register Map and Pub/Sub Communication” checkbox in the <Down-
load Project Data> window, the “ModBus Configuration” and “Sample Data” information for all de-
vices set with the EUI-64 address are sent to the YFGW710. The checkbox is selected by default
if any changes have been made on the Sampling Data or on the ModBus Configuration since the
last download process. The Modbus Client can acquire data regarding to Modbus configuration
without any changes even while the Modbus Register Map is being updated.
l
Devices
In theDevices list of the <Download Project Data> window, the following devices will be selected
by default:
• Devices whose EUI-64 address was set but has not been downloaded yet
• Devices having any changes in settings since the last download.
When a device joins the field wireless network, the concentrator settings are sent to the device.
Then the CO Revision attribute is read from the concentrator object and this value is set in the
Monitoring Host settings (YFGW710).
The CO revision read from the concentrator object in the device via the Field Wireless Configura-
tor is saved in the Project database.
While the Field Wireless Configurator downloads the data to the device, the Field Wireless De-
vice OPC Server can access devices except the target device. The Modbus Client can also read
data related to Modbus configuration. The Field Wireless Configurator can display information on
YFGW710 and devices except the target device.
n
Device Replacement Scenarios
The following describes what data must be downloaded after replacing devices.
l
YFGW710 Replacement
When replacing YFGW710, check all checkboxes at the <Download Project Data> window ex-
cept for “Devices.”
l
Device Replacement
When replacing a device, read the provisioning information file (refer to section C 2.3.3.4). Then
at the <Download Project Data> window, check “Devices,” “Device Provisioning,” and “Modbus
Register Map and Pub/Sub Communication.”