B1-31, Nchecking process data communication, Lother than the above – Yokogawa YFGW710 User Manual

Page 95: Ldata status list

Advertising
background image

<B1. Engineering>

B1-31

IM 01W01F01-01EN

DEV001 download failed due to EUI64 read IDENT_NUMBER configured NG due to timeout!!
Or
DEV001 download failed due to EUI64 read IDENT_NUMBER configured NG due to App(-33)-

server inaccessible for unbuffered request!!
When the above message appears during the download, wait for three minutes, and then per-

form the download to the target device again using Field Wireless Configurator.

l

Other than the above

When the above countermeasures do not remove the error, consult with the responsible depart-

ment of Yokogawa.

n

Checking Process Data Communication

It is possible to check from the page of the [Readings] tab of Field Wireless Management Tool

whether or not the process data communication is being performed.
The last process data that YFGW710 has received from the field wireless device and the time of

day are displayed on the page of the [Readings] tab.
Press the [Search] button. If the timestamp is updated, this means that data is transferred cor-

rectly from the field wireless device to YFGW710.
For details on the operating procedure, refer to C3, Field Wireless Management Tool in Part C of

this document.

l

Parameters displayed on the page of the Readings tab

The parameters about process data communication are defined in the [Sampling Parameters]

field and the parameters are displayed on the page of the [Readings] tab.
When no parameter is set in the Sampling Parameters field, no parameter is displayed on the

page of the Readings tab.

l

Data Status List

When data with data status is assigned to the [Sampling Parameters] field, the data status is also

displayed on the page of the [Readings] tab.
The following shows a Data Status List.

Table B1-13 Data Status

Quality

Substatus

Code

Not Limited

Low Limited

High Limited

Constant

Bad

0

Non-specific

0

0x00

0x01

0x02

0x03

Configuration Error

1

0x04

0x05

0x06

0x07

Device Failure

3

0x0C

0x0D

0x0E

0x0F

Sensor Failure

4

0x10

0x11

0x12

0x13

Out of Service

7

0x1C

0x1D

0x1E

0x1B

Uncertain

1

Non -specific

0

0x40

0x41

0x42

0x43

Sensor Conversion

not Accurate

4

0x50

0x51

0x52

0x53

Good

2

Non-specific

0

0x80

0x81

0x82

0x83

The data status of good (0x80-0x83) means that the function block (e.g. AI) works correctly.
The status of bad or uncertain means that the device does not work normally.

▪ When the status is bad/out of service, the block in question is in the O/S mode. Change the

mode of the block in question to AUTO from PRM.