A3-33, Liecex certification – Yokogawa YFGW710 User Manual

Page 53

Advertising
background image

<A3. YFGW710 Field Wireless Integrated Gateway>

A3-33

IM 01W01F01-01EN

l

IECEx Certification

(1) Technical Data
Model YFGW710 Field Wireless Integrated Gateway with optional code /SN27 is applicable

for use in hazardous locations.

• Applicable standard: IEC60079-0:2011, IEC60079-15:2010, IEC60079-11:2011
• Certificate: IECEx DEK 13.0047
• Type of Protection and Marking Code: Ex nA [ic] IIC T4 Gc
• Ambient Temperature: –40 to 60°C
• IP Code: IP66
• Power Supply: 10.0 V d.c. to 26.4 V d.c.

(Rated voltage: 24.0 V d.c.)

• Overvoltage Category: I
• Power Dissipation: ≤ 10 W
• RF Power: ≤ 20 mW (ISA100.11a; IEEE802.15.4)
• Cable parameters for antenna connection

Cc: 4 nF

Lc: 20 μH

Specific Condition of Use:
Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts.

(2) Electrical Connection
The type of electrical connection is depends on the model code suffix.
The model code suffix is shown on the main label in front of YFGW710.
The second character following the letter A shows the type of electrical connection as below.

Character b on Suffix: Aab-cdefghjkm

The type of electrical connection

2

1/2 NPT female

*1

4

M20 female

*2

Note *1: 1/2 NPT is realized by the conversion adapter from M20 female to 1/2NPT female.

Note *2: When the cable glands or another device are necessary, user needs to prepare them which adapt to M20 female entry.

Advertising