B1.2.3.1 task of setting yfgw710, B1.2.3, B1-16 – Yokogawa YFGW710 User Manual

Page 80: Ndefining modbus register map

Advertising
background image

<B1. Engineering>

B1-16

IM 01W01F01-01EN

n

Defining Modbus Register Map

When communicating with the control system using Modbus communication, this task needs to

be performed.
For details on the procedure to assign to the Modbus Register map, refer to C2, “Field Wireless

Configurator” in Part C of this document.
Only assignment to Input Register is possible for this system. Assignment to Holding Register is

not possible.

TIP

It is only possible to assign the PV value of the device and DIAG_STATUS indicating the diagnostic result of the

device to Input Register.

B1.2.3 Work before Installing Field Wireless Device

This section describes the following tasks that need to be performed for the device and

YFGW710 before the field wireless devices are installed in the field at the plant.

• Task of Setting YFGW710
• Task of Provisioning a Field Wireless Device
• Setting and adjusting field wireless device parameters (this can be performed after installa-

tion)

B1.2.3.1 Task of Setting YFGW710

Before installing YFGW710, the task of setting YFGW710 for connecting by Ethernet is neces-

sary. By factory default, the following values are set to YFGW710.

Table B1-10 YFGW710 Network Parameter Factory Default Values

Item

Default value

IP Address

192.168.0.101

Subnet Mask

255.255.255.0

Default Gateway

192.168.0.1

When changing the YFGW710 network parameter, connect the PC on which Field Wireless Con-

figurator is installed and YFGW710, and follow the instructions described below.
Ensure the IP address of the PC is an IP address other than the factory default IP address of

YFGW710 (namely, an IP address other than 192.168.0.101).