<A3. YFGW710 Field Wireless Integrated Gateway>

A3-27

IM 01W01F01-01EN

l

CSA Certification

Caution for CSA nonincendive/Type n. (Following contents refer to “Doc No. NCS013”)

Note 1. Model YFGW710 Field Wireless Integrated Gateway with optional code /CN17 is appli-

cable for use in hazardous locations.

• Certificate: 2342292
[For CSA C22.2]
• Applicable standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.213,

C22.2 No.61010-1

• Nonincendive for

Class I, Division 2, Groups A, B, C, D.

Class II, Division 2, Groups F, G.

Class III, Division 1

• Enclosure: Type 4X
• Temp. Code: T4
• Ambient Temperature: –40 to 60°C
[For CSA E60079]
• Applicable standard: CAN/CSA E60079-0, CAN/CSA E60079-15, IEC60529:2001
• Ex nA nL IIC T4
• Enclosure: IP66
• Ambient Temperature: –40 to 60°C

Note 2. Electrical Connection

The type of electrical connection is depends on the model code suffix.
The model code suffix is shown on the main label in front of YFGW710.
The second character following the letter A shows the type of electrical connection as below.

Character b on Suffix: Aab-cdefghjkm

The type of electrical connection

2

1/2 NPT female

*1

4

M20 female

*2

Note *1: 1/2 NPT is realized by the conversion adapter from M20 female to 1/2NPT female.

Note *2: When the cable glands or another device are necessary, user needs to prepare them which adapt to M20 female entry.