C2.3.3.5 Downloading Project Data to the YFGW710

To download the project data to the Field Wireless Configurator YFGW710:
1. Click Download in the Tools menu, or click in the toolbar.
2. The Download Project Data window opens (Figure C2-17).

Figure C 2-17

In the left pane of the window, select a Network ID, then select at least one entity you want

to download. In some cases, other entities may be selected automatically.

Necessity for restart after downloading the data is indicated for each entity such as IPv4

Settings (requires restart). The criteria for restart necessity are as follows:
• Changing the IPv4 settings requires restart
• Modifying the channels list for the System Manager requires System Manager restart
• Modifying the Device Tag, Subnet ID, Subnet Mask, and Join Key on the Gateway re-

quires Gateway restart

• Modifying the Device Tag, Subnet ID, Filter Bit Mask, Filter Target ID, and Join Key on

the Backbone router requires restart

3. In the right section of the window, specify the IP Address of the target YFGW710 for con-

necting. The application automatically shows the IPv4 address of YFGW710 for the selected

Network ID.

4. The “Perform error check before downloading” option is enabled by default. An error check

is made during a download, and if any errors are found, the entire download process or part

of it will be aborted depending on the nature of the error. For details of error checks, see

section C2.3.3.6 Error Checks.

5. You can specify if the device information (Vendor ID, Model ID, and Device Tag) will be read

from the device and compared with the information in CF before starting the download.