<A3. YFGW710 Field Wireless Integrated Gateway>

A3-9

IM 01W01F01-01EN

l

Connection Procedure of Power Cable

1. Pull the power cable into the housing of YFGW710 through the power cable ground.
2. Connect + lead wire to + terminal and – lead wire to – terminal.
3. Tighten the terminal screw with a torque of 1.2 to 1.4 N∙m.

NETWORK

SUPPLY

ANTENNA 50Ω

(Optional)

100Base-FX

100Base-FX

TX

RX

SUPPLY

Cable gland for power supply cable

Power supply cable

Power supply terminal

FA0307.ai

Connect the + and – wires to the + and –

terminals, respectively.

If the power cable is a shielded cable, the

shield should be grounded at terminal and

the grounding of the whole cable should be

restricted to this point only.

Fig. A 3-7 Power Supply Cable Connection

A3.2.2 Ground Cable Connection

This section describes ground wiring.
Class D grounding (the third class grounding) with the grounding resistance of 100 Ω or less is

necessary. To connect the grounding cable to YFGW710 directly, use the grounding terminal on

the right bottom of the main body. Do not share the ground wiring with other devices.

IMPORTANT

The explosion proof compliant device always needs the grounding.

l

Applicable Cable (Insulated wire for industrial equipment)

Examples:

• 600 V polyvinyl chloride insulated wires (IV): JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)

Wire Size

• Core: AWG14 to 13 (2 to 2.6 mm

2

)

Terminal Treatment

• Ring terminal for M4: With insulation covers