NORD Drivesystems BU0700 User Manual

Page 100

Advertising
background image

NORDAC SK 700E Operating Manual

100

Subject to technical alterations

BU 0700 GB-1411

Parameter

Setting value / Description / Note

Available with option

P717

Current speed

immer sichtbar

-9999 ... 9999 rpm

Displays the actual motor speed calculated by the FI. Positive values are given for rotation in either
direction.

P718

... - 01

... - 02

... - 03

Current set frequency

always visible

-400 ... 400.0 Hz

Displays the frequency specified by the setpoint. (see also 8.1 Setpoint processing)

... - 01 = Actual setpoint frequency from the setpoint source
... - 02 = Actual setpoint frequency following processing in the inverter status machine
... - 03 = Actual setpoint frequency after the frequency ramp

P719

Actual current

always visible

0 ... 500.0 A

Displays the actual output current.

P720

Actual torque current

always visible

-500.0 ... 500.0 A

Displays the actual calculated torque-developing output current.

-500,0 ... 500.0 A  Negative values = generator, positive values = motor.

P721

Actual field current

always visible

-500.0 ... 500.0 A

Displays the actual calculated field current.

P722

Current voltage

always visible

0 ... 500 V

Displays the actual voltage supplied by the inverter output.

P723

Voltage -d

always visible

0 ... 500 V

Displays the actual field voltage component.

P724

Voltage -q

always visible

-500 ... 500 V

Displays the actual torque voltage component.

P725

Current cos

always visible

0 ... 1.00

Displays the actual calculated power factor of the drive.

P726

Apparent power

always visible

0.00 ... 300.00 kVA

Displays the actual calculated apparent power.

P727

Effective power

always visible

0.00 ... 300.00 kW

Displays the actual calculated effective power.

P728

Input voltage

always visible

0 ... 1000 V

Displays the actual mains voltage at the FI input.

P729

Torque

always visible

-400 ... 400 %

Displays the actual calculated torque.

P730

Field

always visible

0 ... 100 %

Displays the actual field in the motor as calculated by the inverter.

P731

Actual parameter set

always visible

0 ... 3

Displays the actual parameter set.

P732

Phase U current

always visible

0.0 ... 500.0 A

Displays the actual U phase current.

Note: This value can, due to the measurement procedure used even with symmetrical output currents,
deviate somewhat from the value in P719.