List of the possible functions of the digital inputs P420 ... P425

Value Function

Description

Signal

0

No function

Input switched off.

---

1

Enable right

FI supplies output signal, rotation field right (if setpoint positive). 0

1 Flank (P428 = 0)

High

2

Enable left

FI supplies output signal, rotation field left (if setpoint positive). 0

1 Flank (P428 = 0)

High

If automatic start-up is active (P428 = 1), a high level is sufficient.
If the functions "Enabled right" and "Enabled left" are actuated simultaneously, the FI is blocked

3

Change rotation direction

Causes the rotation field to change direction (combined with
Enable right or left).

High

4

Fixed frequency 1

1

The frequency from P429 is added to the setpoint value.

High

5

Fixed frequency 2

1

The frequency from P430 is added to the setpoint value.

High

6

Fixed frequency 3

1

The frequency from P431 is added to the setpoint value.

High

7

Fixed frequency 4

1

The frequency from P432 is added to the setpoint value.

High

If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In addition, the
analog setpoint (including minimum frequency) is added.

8

Parameter set switch Bit 0

Selection of the active Bit 0 parameter set (see P100)

High

9

Maintain the frequency

During the start-up or braking phase, a low level will cause the
output frequency to be "held". A high level allows the ramp to
proceed.

Low

10

Voltage disable

2

The FI output voltage is switched off and the motor runs freely to
a stop.

Low

11

Quick stop

2

The inverter reduces the frequency according to the programmed
emergency stop time (P426).

Low

12

Fault acknowledgement 2

Error acknowledgement with an external signal. If this function is
not programmed, an error can also be acknowledged by a low
enable setting.

01

Flank

13

PTC resistor input

2

Analog evaluation of the present signal switching threshold,
approx. 2.5 Volt. 2sec delayed E002 message.

Analog

14

Remote control

With Bus system control, low level switches the control to control
via control terminals.

High

15

Jog frequency

This frequency fixed value can be set using the HIGHER /
LOWER and ENTER keys.

High

16

Motor potentiometer

As setting value 09, is however not maintained below the
minimum frequency and above the maximum frequency.

Low

17

Parameter set switch Bit 1

Selection of the active parameter set Bit 2 (see P100).

High

18

Watchdog

2

Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Starting is with the first high flank.

01

Flank

19

Setpoint 1 on/off

Analog input switch-on and switch-off 1 (High = ON)

High

20

Setpoint 2 on/off

Analog input switch-on and switch-off 2 (High = ON)

High

21

Fixed frequency 5

1

The frequency from P433 is added to the setpoint.

High

22

Approach reference point

PosiCon option (see manual BU 0710)

High

23

Reference Point

PosiCon option (see manual BU 0710)

High

24

Teach-In

PosiCon option (see manual BU 0710)

High

25

Quit Teach-In

PosiCon option (see manual BU 0710)

High

These functions are only available with the PosiCon Special Extension Unit!

... continued on the next page