NORD Drivesystems BU0700 User Manual

Page 31

Advertising
background image

3.1 Technology unit

BU 0700 GB-1411

Subject to technical alterations

31

Display

Error

Cause

Remedy

Identification error

220

UNRECOGNISED DEVICE

Device ID not found.
The connected inverter is not listed in the database of the ParameterBox; no
communication can be established.

Please contact your Getriebebau Nord dealership.

221

SOFTWARE VERSION NOT RECOGNISED

Software version not found.
The software of the connected inverter is not listed in the ParameterBox
database, no communication can be set up.

Please contact your Getriebebau Nord dealership.

222

CONFIGURATION STAGE NOT
RECOGNISED

An unknown component has been detected in the frequency inverter (Customer
unit / Special extension unit).

Please check the components installed in the frequency inverter

If necessary check the software version of the ParameterBox and the

frequency inverter.

223

BUS CONFIGURATION HAS CHANGED

A different device to that saved responds when the last bus configuration is
restored.
This error can only occur if the parameter >Auto. Bus Scan< is set to OFF and
another device has been connected to the ParameterBox.

Activate the Automatic Bus Scan function.

224

DEVICE NOT SUPPORTED

The inverter type entered in the ParameterBox is not supported!

The ParameterBox cannot be used with this inverter.

225

THE CONNECTION TO THE INVERTER IS
BLOCKED

Access to a device that is not online (previously Time Out error).

Carry out a bus scan via the parameter >Bus Scan< (P1001).

ParameterBox operating error

226

SOURCE AND TARGET ARE DIFFERENT
DEVICES

Copying objects of different types (from / to different inverters) is not possible.

227

SOURCE IS EMPTY

Copying of data from a deleted (empty) storage medium

228

THIS COMBINATION IS NOT PERMITTED

Target and source for the copying function are the same. The command cannot
be carried out.

229

THE SELECTED ITEM IS EMPTY

Parameterisation attempt of a deleted storage medium

230

DIFFERENT SOFTWARE VERSIONS

Warning
Copying objects with different software versions can lead to problems when
transferring parameters.

231

INVALID PASSWORD

Attempt to alter a parameter without a valid Box password being entered in
parameter >Box Password< P 1306.

232

BUS SCAN ONLY WHEN IN ONLINE MODE
ONLINE

A bus scan (search for a connected frequency inverter) is only possible when in
ONLINE mode.

Advertising