NORD Drivesystems BU0700 User Manual

Page 94

Advertising
background image

NORDAC SK 700E Operating Manual

94

Subject to technical alterations

BU 0700 GB-1411

Parameter

Setting value / Description / Note

Available with option

P541

Set relays

BSC STD MLT BUS

000000 ... 111111

[ 000000 ]

This function provides the opportunity to control the relay and the digital outputs independently of the FI
status. To do this, the relevant output must be set to the function External control.

This function is binary coded: Setting range [ 000000-111111 (Binary)]

Bit 0 = Relay 1
Bit 1 = Relay 2
Bit 2 = Analog output 1 (Digital function)
Bit 3 = Analog output 2 (Digital function)
Bit 4 = Relay 3
Bit 5 = Relay 4
This function can either be used manually or in combination with a Bus control with this parameter
(Function test).

BUS: The corresponding value is written into the parameter, thereby setting the relay and digital
outputs.

ControlBox: The Control Box enables the selection of all output combinations. If only Bits 0 - 3 are to
be activated, the selection is displayed in binary code. If the option PosiCon is installed (Bit 4 + 5), the
display is coded in hexadecimal.

ParameterBox: Each individual output can be separately picked and activated.

P542

.. - 01

.. - 02

Set analog output 1...2

STD MLT

0.0 ... 10.0 V

[ 0.0 ]

This function provides the opportunity to control the analog outputs of the FI (depending on the option)
independently of its actual operating status. To do this, the relevant output (P418/P448) must be set to
the function External control (=7).

This function can either be used manually or in combination with a Bus control with this parameter. The
value set here will, once confirmed, be output at the analog output .

When programming with the ControlBox:

P_ 0 1

P542

P_ 0 2

0 . 0

0 . 0

Setting:
Analog output 1

Setting:
Analog output 2

ENTER

ENTER

ENTER

VALUE

P543 (P)

Bus actual value 1

always visible

0 ... 12

[ 1 ]

The return value 1 can be selected for bus actuation in this parameter.

Note: Further details can be found in the respective BUS operating instructions or in parameter P400.

0 = Off
1 = Current frequency
2 = Current speed
3 = Current
4 = Torque current
5 = State digital

IO’s

1

6 = Current position (with PosiCon, SK 700E only)
7 = Set position (with PosiCon SK 700E only)
8 = Nominal frequency
9 = Error code
10 = Current position increment

2

(with PosiCon SK 700E

only)

11 = Set position increment

2

(with PosiCon SK 700E only)

12 = Bus IO Out Bits 1-7

1

The assignment of the dig. inputs in P543/ 544/ 545 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6

Bit 6 = DigIn 7

Bit 7 = DigIn 8

Bit 8 = DigIn 9

Bit 9 = DigIn 10

Bit 10 = DigIn 11

Bit 11 = DigIn 12

Bit 12 = Rel 1

Bit 13 = Rel 2

Bit 14 = Rel 3

Bit 15 = Rel 4

2

The setpoint/actual position corresponding to an 8192 increment encoder. According to the setting in (P546) 16 Bit or 32 Bit

setpoint position) the setting to 16 Bit or 32 Bit values is carried out automatically.