NORDAC SK 700E Operating Manual

32

Subject to technical alterations

BU 0700 GB-1411

Display

Error

Cause

Remedy

Warnings

240

OVERWRITE DATA?

 YES

NO

These warnings indicate that there is a possibly significant change which needs
additional confirmation.
Once the next procedure has been selected, it must be confirmed with the
"ENTER" key.

241

DELETE DATA?

 YES

NO

242

MOVE SW VERSION?

 CONTINUE

CANCEL

243

MOVE SERIES?

 CONTINUE

CANCEL

244

DELETE ALL DATA?

 YES

NO

Inverter control error

250

THIS FUNCTION IS NOT ENABLED

The function requested is not enabled at the frequency inverter parameter
interface.

Change the value of the parameter >Interface< of the connected inverter to

the required function.
More detailed information can be obtained from the operating instructions for
the frequency inverter.

251

CONTROL COMMAND WAS NOT
SUCCESSFUL

The control command could not be implemented by the inverter, as a higher
priority function, e.g. Emergency Stop or an OFF signal to the control terminals of
the inverter, is present

252

CONTROL OFFLINE NOT POSSIBLE

Call up of a control function in Offline mode.

Change the operating mode of the p-box in the parameter >Operating Mode<

P1302 to Online and repeat the action.

253

ERROR ACKNOWLEDGEMENT NOT
SUCCESSFUL

The acknowledgement of an error at the frequency inverter was not successful,
the error message remains.

Error message from inverter

"ERROR No. FROM INVERTER"

INVERTER FAULT "INVERTER FAULT TEXT"

An error has occurred at the frequency inverter with the displayed number. The
inverter error number and text are displayed.