8.2.2 Process controller parameter settings

(Example: Setpoint frequency: 50Hz, control limits: +/- 25%)

P105 (maximum frequency) [Hz]

:

 

 

 

100%

%

P415

Hz

freq.

Setpoint

Hz

freq.

Setpoint

: E.g.

%

100

%

25

50

50

Hz

Hz

62.5 Hz

P400 (Funct. analog input)

:

“4” (frequency addition)

P411 (setpoint frequency) [Hz]

: Set frequency with 10 V at analog input 1

: E.g. 50 Hz

P412 (Process controller setpoint)

: CR middle position / Default setting 5 V (adapt if necessary)

P413 (P controller) [%]

: Factory setting 10% (adapt if necessary)

P414 (I-controller) [% / ms]

: recommended

ms

%

10

.

0

P415 (limitation +/-) [%]

: Controller limitation (see above)

Note:

In the function process controller, parameter P415 is used as a controller
limiter downstream from the PI controller. This parameter therefore has a
double function.

Example 25% of setpoint

P416 (ramp before controller) [s]

: Factory setting 2s (if necessary, adjust to controller behaviour)

P420 (Funct. Switch digital input 1)

: "1" Enable right

P421 (Funct. Switch digital input 2)

: "40" actual value PID process controller (only with Basic I/O or Standard I/O)

Alternatively, the 2

nd

analog input (P405=14) of the multi I/O can be used.