NORDAC SK 700E Operating Manual

86

Subject to technical alterations

BU 0700 GB-1411

Parameter

Setting value / Description / Note

Available with option

P435 (P)

Relay 1 scaling

BSC STD MLT BUS

-400 ... 400 %

[ 100 ]

Adjustment of the limit values of the relay functions. For a negative value, the output function will be
output negative.

Current limit = x [%]

P203 >Motor nominal current<

Torque current limit = x [%]

P203

P206 (calculated motor nominal torque)

Frequency limit= x [%]

P201 >Motor nominal frequency<

Values in the +/-20% range are limited internally to 20%.

P436 (P)

Relay 1 hysteresis

BSC STD MLT BUS

0 ... 100 %

[ 10 ]

Difference between switch-on and switch-off point to prevent oscillation of the output signal.

P441 (P)

Relay 2 function

STD MLT

0 ... 38

[ 7 ]

This parameter is identical to P434, but refers to P442, P443.

P442 (P)

Relay 2 scaling

STD MLT

-400 ... 400 %

[ 100 ]

This parameter is identical to P435, but refers to P441, P443.

P443 (P)

Relay 2 hysteresis

STD MLT

0 ... 100 %

[ 10 ]

This parameter is identical to P436, but refers to P441, P442.

P447 (P)

Offset analog output 2

MLT

-10.0 ... 10.0 V

[ 0.0 ]

This parameter is identical to P417, but refers to P418, P419.

P448 (P)

Function analog output 2

MLT

0 ... 52

[ 0 ]

This parameter is identical to P418, but refers to P417, P419.

P449 (P)

Standardisation analog output 2

MLT

-500 ... 500 %

[ 100 ]

This parameter is identical to P419, but refers to P417, P418.

P458

.. - 01

.. - 02

Analog output mode

MLT

0 ... 1

[ 0 ]

0 = 0...10V / 0...20mA

1 = 2...10V / 4...20mA

This parameter determines the working range of the respective analog
output. Array 01 stands for the 1st analog output, Array 02 for the 2nd.

P460

Watchdog time

always visible

0.0

0.1 ... 250.0 s

[ 10.0 ]

The time interval between the expected watchdog signals (programmable function of digital inputs
P420 ... P425). If this time interval elapses without an impulse being registered, switch off and error
message E012 are actuated.

0.0 (customer error): Customer error function, as soon as a low-high flank is registered at the input,

the FI switches off with error E012.