3 multi i/o – NORD Drivesystems BU0700 User Manual

Page 47

Advertising
background image

3.2 Customer unit

BU 0700 GB-1411

Subject to technical alterations

47

3.2.3 Multi I/O

(SK CU1-MLT, Option)

The Multi I/O Customer Unit provides the highest functionality of digital and analog
signal processing. 2 analog inputs and 6 digital outputs are available to control the
frequency inverter. Both analog inputs can process signals from 0...10V, 0...20mA
(4...20mA) or -10V...+10V.

Two programmable and scalable analog outputs 0...10V enable actual operating
parameters to be transmitted to a display device or process control system.

By means of the two relay contacts, brake control and even warnings to another
system can be initiated.

The digital inputs of the multi I/O cannot process analog setpoints! (See also Chap.
5.1.5, P420-P425)

Connector

Functions

Maximum

cross-section

Parameter

X2.1

Output relay

1.5 mm

2

P434 ... P443

X2.2

Analog signals IN / OUT

1.0 mm

2

P400 ... P419

X2.3

Digital inputs

1.0 mm

2

P420 ... P425
























NOTE: All control voltages are based on a common reference potential!

Potentials AGND /0V und GND /0V are internally linked in the device.

The maximum total current 5/15V is 300mA!

Analog output of PLC:

0...10V / -10...+10 V

or potentiometer: 2...10k

Floating contact or
PLC output: 7,5...33V

Output relay:
max. 2,0A
28V DC /230 V AC

Analog inputs 1 and 2:

-10...+10V, 0/4...20mA

Power supply: 5V

Analog outputs 1 and 2:

0...10V / max. 5mA

U

REF

= 10 V / I

max

= 10 mA

Power supply: 15V

DIG IN 6 only = Temperature sensor!

Switching threshold = 2,5 V

Digital inputs:

DIG IN 1 = On right

DIG IN 2 = On left

DIG IN 3 = Parameter set bit 0

DIG IN 4 = Fixed frequency 1

DIG IN 5 / 6 = No function

X

2

.1

X

2

.2

X

2

.3

11 VREF 10V
12 AGND /0V
14 AIN1 +

16 AIN2 +
17 AOUT1

21 DIG IN 1
22 DIG IN 2

23 DIG IN 3

24 DIG IN 4

42 VO +15V

01 REL1.1

02 REL1.2

03 REL2.1

04 REL2.2

25 DIG IN 5

26 DIG IN 6

18 AOUT2
40 GND /0V

41 VO +5V

Additional burden resistance for

0/4...20mA analog input 1 (250

)

Additional burden resistance for

0/4...20mA analog input 2 (250

)

WARNING / NOTE

It is not permissible to connect the output relay of the Customer Unit (SK CU...and SK XU) to dangerous
voltages(

≥60VAC) if a contact of the relay is connected to a circuit with safe isolation.

ON OFF

Analog input 1

ON = Current, OFF = Voltage

Analog input 2

ON = Current, OFF = Voltage

U/I Switching, R = 250