NORD Drivesystems BU0700 User Manual

Page 18

Advertising
background image

NORDAC SK 700E Operating Manual

18

Subject to technical alterations

BU 0700 GB-1411

-ZW BR +ZW PE

PE L1 L2 L3

M

3 ~

L3

L2

L1

PE

Input

PE

W

U V

Output

BR

2.10.2 Mains connection up to 22kW (PE/L1/L2/L3)

No special safety devices are required on the mains input side for
the frequency inverter, just the normal mains protection (see
technical data) and a master switch/fuse.

Connection terminals cross-section:

SK 700E-151-340-A ...
SK 700E-751-340-A

VDE

4mm²

(0.5 … 0.6Nm)

UL/cUL

(AWG 24-10)

SK 700E-112-340-A ...
SK 700E-152-340-A

VDE

10mm²

(1.2 … 1.5Nm)

UL/cUL

(AWG 22-8)

SK 700E-182-340-A ...
SK 700E-222-340-A

VDE

25mm²

(2.4 … 4.0Nm)

UL/cUL

(AWG 16-4)

Note:

The use of this inverter on an IT network is possible
after minor alterations. Please consult your supplier.

2.10.3 Mains connection from 30kW (PE/L1/L2/L3)

No special safety devices are required on the mains input side for
the frequency inverter, just the normal mains protection (see
technical data) and a master switch/fuse.

Connection terminals cross-section:

SK 700E-302-340-O ...
SK 700E-372-340-O

VDE

35mm²

(6 … 8Nm)

(PE terminals = 16mm

2

)

UL/cUL

(AWG 2)

SK 700E-452-340-O ...
SK 700E-552-340-O

VDE

25-50mm²

(6 … 8Nm)

UL/cUL

(AWG 4-0)

SK 700E-752-340-O

VDE

95mm²

(15 … 20Nm)

SK 700E-902-340-O

UL/cUL

(AWG 000)

SK 700E-113-340-O ...
SK 700E-163-340-O

VDE 50-150mm²

(25 … 30Nm)

(PE terminals = 35-95mm

2

) UL/cUL

(AWG 0-300 MCM)

Note:

The use of this inverter on an IT network is possible
after minor alterations. Please consult your supplier.

Note:

Only one PE terminal is located near the mains connection in the 90kW
device. Further PE connections can be implemented on the device housing.

PE L1 L2 L3

M

3 ~

L3

L2

L1

PE

Input

+B -B

Brake

-DC

PE

W

U V

Output

Brake resistor

Optional, Chap. 2.7/2.8

Brake resistor

Optional, Chap. 2.7/2.8

Some of the PE connections are in the support

plate, near to the terminal bar

Do not use ZW, the
connection is sealed.