2 basic parameters – NORD Drivesystems BU0700 User Manual

Page 64

Advertising
background image

NORDAC SK 700E Operating Manual

64

Subject to technical alterations

BU 0700 GB-1411

5.1.2 Basic parameters

Parameter

Setting value / Description / Note

Available in Option

P100

Parameter set

always visible

0 ... 3

[ 0 ]

Selection of the parameters sets to be parameterised. 4 parameter sets are available. All parameter
set-dependent parameters are identified by (P).

The selection of the operating parameter set is done via a digital input or the Bus control. Switching
can take place during operation (online).

Setting

Digital input

function [8]

Digital input

function [17]

Display

ControlBox

0 = Parameter set 1

LOW

LOW

1

2

1 = Parameter set 2

HIGH

LOW

2

1

2 = Parameter set 3

LOW

HIGH

1

2

3 = Parameter set 4

HIGH

HIGH

2

1

If enabled via the keyboard (ControlBox, PotentiometerBox or ParameterBox), the operating parameter
set will match the settings in P100.

P101

Copy parameter set

always visible

0 ... 4

[ 0 ]

After confirmation with the ENTER key, a copy of the parameter set selected in P100 >Parameter set<
is written to the parameter set dependent on the value selected here

0 = Results in no action.

1 = Copies the active parameter set to parameter set 1

2 = Copies the active parameter set to parameter set 2

3 = Copies the active parameter set to parameter set 3

4 = Copies the active parameter set to parameter set 4

P102 (P)

Acceleration time

always visible

0 ... 320.00 s

[ 2.00 ]

> 11kW [ 3.00 ]

> 22kW [ 5.00 ]

Acceleration time is the time corresponding to the linear frequency rise from 0Hz to the set maximum
frequency (P105). If an actual setpoint of <100% is being used, the acceleration time is reduced
linearly according to the setpoint set.

The start-up time can be extended by certain circumstances, e.g. FI overload, setpoint lag, rounding or
if the current limit is reached.

P103 (P)

Deceleration time

always visible

0 ... 320.00 s

[ 2.00 ]

> 11kW [ 3.00 ]

> 22kW [ 5.00 ]

Deceleration time is the time corresponding to the linear frequency reduction from the set maximum
frequency to 0Hz (P105). If an actual setpoint <100% is being used, the deceleration time reduces
accordingly.

The deceleration time can be extended by certain circumstances, e.g. by the selected >Switch-off
mode< (P108) or >Ramp smoothing< (P106).

P104 (P)

Minimum frequency

always visible

0.0 ... 400.0 Hz

[ 0.0 ]

The minimum frequency is the frequency supplied by the FI as soon as it is enabled and no additional
setpoint is set.

In combination with other setpoints (e.g. analog setpoint or fixed frequencies) these are added to the
set minimum frequency.

This frequency is undershot when

a) the drive is accelerated from standstill.

b) The FI is blocked. The frequency then reduces to the absolute minimum (P505) before it is

blocked.

c) The FI is reversing. The reverse in the rotation field takes place at the absolute minimum

frequency (P505).

This frequency can be continuously undershot if, during acceleration or deceleration, the function
"Maintain frequency" (Function Digital input = 9) is executed.