NORD Drivesystems BU0700 User Manual

Page 34

Advertising
background image

NORDAC SK 700E Operating Manual

34

Subject to technical alterations

BU 0700 GB-1411

Controlling the frequency inverter with the ControlBox

The inverter can only be controlled via the ControlBox, if it has not previously been enabled via the control terminals or via a
serial interface (P509 = 0).

If the "START" key is pressed, the inverter in the operating display changes (selection P001).

The frequency inverter supplies 0Hz or a minimum frequency (P104) or jog frequency (P113) that has been set at a higher level.

vector

R

STOP

Store current frequency

as jog frequency

Set frequency = 0Hz

(press simultaneously)

Increase frequency

Change rotation direction

Decrease frequency

START

Parameter set display

Quick stop

(press simultaneously)

Parameter set display:

The LEDs indicate the actual operating parameter set in the operating display (P000) and the current parameter set being
parameterised (

P000). There, the display appears in binary form.

The parameter set can also be changed during operation via the parameter P100 (control via ControlBox).

Frequency setpoint:

The current frequency setpoint depends on the setting in the parameters jog frequency (P113) and minimum frequency (P104).

This value can be altered during keyboard operation with the value keys

and

and permanently stored in P113 as the

jog frequency by pressing the ENTER key.

Quick stop:

By simultaneously pressing the STOP key

and the "Change direction key”

, an quick stop can be initiated.