5.1.2 Basic parameters

BU 0700 GB-1411

Subject to technical alterations

65

Parameter

Setting value / Description / Note

Available in Option

P105 (P)

Maximum frequency

always visible

0.1 ... 400.0 Hz

[ 50.0 ]

The frequency supplied by the FI after being enabled and once the maximum setpoint is present, e.g.
analog setpoint as per P403, a correspondingly fixed frequency or maximum via the ControlBox.

This frequency can only be overshot by the slip compensation (P212), the function "Maintain
frequency" (function digital input = 9) or a change to another parameter set with lower maximum
frequency.

P106 (P)

Ramp smoothing

always visible

0 ... 100 %

[ 0 ]

This parameter enables a smoothing of the acceleration and deceleration ramps. This is necessary for
applications where gentle, but dynamic speed change is important.

Ramp smoothing is carried out for every setpoint change.

The value to be set is based on the set acceleration and deceleration time, however values <10% have
no effect.

The following then applies for the entire acceleration or deceleration time, including rounding:

 

100%

%

P106

t

t

t

P102

P102

TIME

ATION

ACCELER

tot

 

100%

%

P106

t

t

t

P102

P102

TIME

ON

DECELERATI

tot

P102

P103

Output

frequency

Setpoint

frequency

Time

each

10 – 100% from P102

each

10 – 100% from P103