P410 (p), Minimum frequency analog input 1/2, P411 (p) – NORD Drivesystems BU0700 User Manual

Page 79: Maximum frequency analog input 1/2, P412 (p), Nominal value process controller, P413 (p), Pid control p-component, P414 (p), Pid control i-component

Advertising
background image

5.1.5 Control terminals

BU 0700 GB-1411

Subject to technical alterations

79

Parameter

Setting value / Description / Note

Available with option

P410 (P)

Minimum frequency analog input 1/2

always visible

0.0 ... 400.0 Hz

[ 0.0 ]

The minimum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies that have also been entered into the inverter for additional
functions. Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Minimum frequency above analog setpoint (potentiometer) Process controller

P411 (P)

Maximum frequency analog input 1/2

always visible

0.0 ... 400.0 Hz

[ 50.0 ]

The maximum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies that have also been entered into the inverter for additional
functions. Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Maximum frequency above analog setpoint (potentiometer) Process controller

P412 (P)

Nominal value process controller

always visible

0.0 ... 10.0 V

[ 5.0 ]

Fixed specification of a setpoint for the process controller that will only occasionally be altered.

Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 8.2

P413 (P)

PID control P-component

always visible

0 ... 400.0 %

[ 10.0 ]

Only effective if the function Actual frequency PID is selected.

The P-component of the PID controller determines the frequency jump if there is a rule deviation based
on the rule difference.

For example: At a setting of P413 = 10% and a rule difference of 50%, 5% is added to the actual
setpoint.

P414 (P)

PID control I-component

always visible

0 ... 300.0

‰ / ms

[ 1.0 ]

Only effective if the function Actual frequency PID is selected.

The I-component of the PID controller determines the frequency change, dependent on time.

P415 (P)

PID control D-component

always visible

0 ... 400.0 %ms

[ 1.0 ]

Only effective if the function Actual frequency PID is selected.

If there is a rule deviation, the D-component of the PID controller determines the frequency change
multiplied by time.

P416 (P)

Ramptime PID setpoint

always visible

0 ... 99.99s

[ 2.00 ]

Only effective when the function Actual frequency PID is selected.

Ramp for PID setpoint

PID controller

P413 (P-component)

P414 ( I-component)

P415 (D-component)

Frequency ramp

P102, P103

Ramp setpoint

P416

Maximum frequency P105

(monitored, limited)

Maximum frequency P105

(unlimited)

Minimum frequency P104

(monitored, limited)

- Maximum frequency P105

(unlimited)

Maximum

frequency P105

Minimum

frequency P104

Maximum frequency

auxiliary setpoint P410

Minimum frequency

auxiliary setpoint P411

Analog input 1

Analog input 2

Bus setpoint 3

Bus setpoint 2

Inc

Auxiliary

setpoint sources

PotentiometerBox

P400-P404

Scaling

P405-P409

Scaling

Analog input 1

Analog input 2

Bus setpoint 1,2,3

Main

setpoint sources

Fixed frequency 1-5

Controlbox /

PotentiometerBox

Jog frequency

P400-P404

Scaling

P405-P409

Scaling

Also in

combination, se e

se tpoint adjustme nt

P417 (P)

Offset analog output 1

STD MLT

-10.0 ... +10.0 V

[ 0.0 ]

In the analog output function an offset can be entered to simplify the processing of the analog signal in
other equipment.

If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).