NORDAC SK 700E Operating Manual

12

Subject to technical alterations

BU 0700 GB-1411

2.5 Line choke (accessories)

To reduce input side current harmonics, additional inductivity
can be installed into the line supply to the inverter.

These chokes are specified for a maximum supply voltage of
480V at 50/60 Hz.

The protection class of the chokes is IP00 and they must
therefore be installed in a control cabinet.

For frequency inverters with an output of 45 kW or more, a
line choke is recommended where several devices are being
used, in order to avoid possible adverse effects of one device
on another. In addition, the charging currents (mains voltage
fluctuations) are significantly reduced.

Inverter type

NORDAC

SK 700E

Input choke 3 x 380 - 480 V

Length

L1

Width

B1

Depth

T

Detail: mounting

Conn

e

c

tio

n

Type

Permanent

current

Inductance

Length

L2

Width

B2

M

ou

nti

n

g

1.5 ... 2.2 kW

SK CI1-460/6-C

6 A

3 x 4.88 mH

71

125

140

55

100

M4

4

3.0 ... 4.0 kW

SK CI1-460/11-C

11 A

3 x 2.93 mH

84

155

160

56.5

130

M6

4

5.5 ... 7.5 kW

SK CI1-460/20-C

20 A

3 x 1.47 mH

98

190

201

57.5

170

M6

10

11 ... 18.5 kW

SK CI1-460/40-C

40 A

3 x 0.73 mH

118

190

201

77.5

170

M6

10

22 ... 30 kW

SK CI1-460/70-C

70 A

3 x 0.47 mH

124

230

220

98

180

M6

35

37 ... 45 kW SK CI1-460/100-C

100 A

3 x 0.29 mH

148

230

290

122

180

M6

50

55 ... 75 kW SK CI1-460/160-C

160 A

3 x 0.18 mH

170

299

360

105

237

M8

95

90 ... 132 kW SK CI1-460/280-C

280 A

3 x 0.10 mH

190

290

270

133

240

M10

150

160 kW SK CI1-460/350-C

350 A

3 x 0.084 mH

190

300

270

107

224

M8

CU Bar

All dimensions in [mm]

[mm

2

]

T

B2

B1

L1

L2

1

3

4

2

5

6