NORD Drivesystems BU0700 User Manual

Page 99

Advertising
background image

5.1.8 Information

BU 0700 GB-1411

Subject to technical alterations

99

Parameter

Setting value / Description / Note

Available with option

P706

.. - 01

...

.. - 05

Parameter set last error 1...5

always visible

0 ... 3

This parameter stores the parameter set code that was active when the error occurred. Data for the
previous 5 faults are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.

P707

.. - 01

.. - 02

Software version

always visible

0 ... 9999

Contains the software status of the frequency inverter and
cannot be changed.

... - 01 = Version number (3.0)

... - 02 = Revision number (0)

P708

State of digital inputs

always visible

00 ... 3F
(hexadecimal)

Displays the status of the digital inputs in hexadecimal code. This display can be used to check the
input signals.

Bit 0 = Digital input 1

Bit 1 = Digital input 2

Bit 2 = Digital input 3

Bit 3 = Digital input 4

Bit 4 = Digital input 5

Bit 5 = Digital input 6

Bit 6 = Digital input 7 (only with PosiCon)

Bit 7 = Digital input 8 (only with PosiCon)

Bit 8 = Digital input 9 (only with PosiCon)

Bit 9 = Digital input 10 (only with PosiCon)

Bit 10 = Digital input 11 (only with PosiCon)

Bit 11 = Digital input 12 (only with PosiCon)

Bit 12 = Digital input 13 (only with encoder)

ControlBox: If just four digital inputs are present, then the status is displayed in binary. If the
Customer Unit Multi I/O, Encoder or PosiCon is installed (Bit 4, 5 ...), the display is coded in
hexadecimal.

P709

Voltage analog input 1

BSC STD MLT

-10.0 ... 10.0 V

Displays the measured analog input value 1. (-10,0 ... 10.0V)

P710

Voltage analog output 1

STD MLT

0.0 ... 10.0V

Displays the delivered value of analog output 1. (0,0 ... 10.0V)

P711

State of relays

always visible

00 ... 11 (binary)

Displays the actual status of the signal relays.

Bit 0 = Relay 1

Bit 1 = Relay 2

Bit 2 = Relay 3 (Option PosiCon)

Bit 3 = Relay 4 (Option PosiCon)

P712

Voltage analog input 2

MLT

-10.0 ... 10.0 V

Displays the measured analog input value 2. (-10,0 ... 10.0V)

P713

Voltage analog output 2

MLT

0.0 ... 10.0V

Displays the delivered value of analog output 2. (0,0 ... 10.0V)

P714

Opetaring time

always visible

0.0 ... 9999.1 h

Time that the FI has voltage applied and is operational.

P715

Running time

always visible

0.0 ... 9999.1 h

Time during which the FI was enabled.

P716

Current frequency

always visible

-400 ... 400.0 Hz

Displays the actual output frequency.