8 Additional information

BU 0700 GB-1411

Subject to technical alterations

123

NOTE:

Please note that these limit value classes are only reached if the standard switching frequency (4/6kHz) is being used and the
length of the shielded motor cable does not exceed the limits.

In addition, it is essential to use wiring suitable for EMC. (Control cabinet / Cable clamping)

The motor cable shielding must be applied on both sides (inverter shield angle and the metal motor terminal box). To comply
with Class 3, cable shielding must also be applied at the entry to the control cabinet (EMC screw connection).

Overview of standards that, as per EN 61800-3 (product standard for frequency inverters) are

based on EN 50081; 510082 and must be complied with

Standard

Limit value class

Emission of interference

Cable based interferences

EN55011

"A"

"B" with filter

Radiated interference

EN55011

"A"

"B" with filter, built into control cabinet

Immunity from interference

DSE

EN61000-4-2

8kV (AD & CD)

Burst on control cables

EN61000-4-4

1kV

Burst on mains and motor cables

EN61000-4-4

2kV

Surge (phase-phase / phase-ground)

EN61000-4-5

1kV / 2kV

EMF

EN61000-4-3

10V/m; 26-1000MHz

Voltage fluctuations and drops

EN61000-2-1

+10%, -15%; 90%

Voltage asymmetries and frequency

changes

EN61000-2-4

3%; 2%

Wiring recommendations for compliance with Class 3

M

3 ~

PE

L

1

W

V

U

W

V

U

380-480V

50-60Hz

L

1

L

2

PE

L

2

L

3

L

3

PE

+UZW/-B

BR/+B

NORDAC SK 700E

Aux. mains

filter

Shield angle

Brake resistor

(Accessories)