6 Error messages

BU 0700 GB-1411

Subject to technical alterations

111

Display

Error

Cause

Remedy

Group

Detail in
P700 / P701

8.3

Customer unit type incorrect

8.4

Database number incorrect

8.7

Original and reflection are not
identical

8.9

ControlBox error

SK-TU1-CTR memory is too small.

 Replace ControlBox

E009

---

ControlBox error

SPI Bus faulty, no communication with ControlBox.

 Check ControlBox for correct position.

 Switch mains voltage off and on again.

E010

10.0

Telegram downtime
(P513)

 Telegram transfer is faulty, check external connection.

 Check Bus Protocol program process.

 Check Bus master.

10.2

External bus module telegram
time-out

10.4

External bus module initialisation
failure

 Check P746.

 Bus module not correctly plugged in.

 Check Bus module current supply.

10.1

External Bus module system
failure

Further details can be found in the respective additional BUS
operating instructions.

10.3

10.5

10.6

10.7

10.8

External module communication
error

Connection error/external module error, evaluation delayed by 1
sec, only when mains voltage present.

E011

11.0

Customer unit (SK CU1-...)

Reference voltage of customer unit faulty (10V/15V). Only
displayed if control is via the control terminals (P509 = 0/1).

 Check control terminals connection for short-circuit.

 I/O module may not be correctly engaged

E012

12.0

Customer Watchdog

The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for longer
than the time set in parameter P460 >Watchdog time<.

E013

13.0

Encoder error

Encoder error (only for special extension unit Encoder/PosiCon)

 5V Sense signal not present at encoder input

13.1

Speed slip error

 Slip error reached (P327), increase value.