Display

Error

Cause

Remedy

Group

Detail in
P700 / P701

13.2

Slip error switch-off monitoring

"Safe stop" was carried out

 Torque limit (P112) was reached, switch-off or increase as

necessary.

 Current limit (P536) was reached, switch-off or increase as

necessary.

 Check motor data (motor circuit, stator resistance)

 If necessary, check incremental encoder data (P3xx)

E014

14.0

Slave check

PosiCon - Error 1

Further details can be found in the description BU 0710

14.1

Host check

14.2

Reference point travel error

14.3

Absolute encoder voltage
monitoring bit

14.4

Absolute encoder error

14.5

Position change and speed do
not match

14.6

Slip error between absolute and
incremental encoders

14.7

Maximum position exceeded

14.8

Minimum position undershot

E015

15.0

Incorrect software version

PosiCon - Error 2

Further details can be found in the description BU 0710

15.1

Watchdog PosiCon

15.2

Stack overflow PosiCon

15.3

Stack underflow PosiCon

15.4

Undefined opcode PosiCon

15.5

Protected instruction PosiCon

15.6

Illegal word access PosiCon

15.7

Illegal instruction access PosiCon

15.8

EPROM error PosiCon

E016

16.0

Motor phase error

 A motor phase is not connected.
 Check P539

16.1

Motor current monitoring for
braking mode

Required exciting current not achieved at moment of switch-on.

 Check P539
 Check motor connection

E017

17.0

Customer unit change

New or missing customer unit

 Switch mains voltage off and then on again