Parameter

Setting value / Description / Note

Available with option

P505 (P)

Abs. minimum frequency

always visible

0.0 ... 10.0 Hz

[ 2.0 ]

Gives the frequency value that cannot be undershot by the inverter.

At the absolute minimum frequency, braking control (P434 or P441) and the setpoint delay (P107) are
actuated. If a setting value of "Zero" is selected, the brake relay does not switch during reversing.

When controlling lift equipment, this value should be set at a minimum of 2.0Hz. From approx. 2Hz the
current control of the FI operates and a connected motor can supply sufficient torque.

P506

Automatic acknowledgement

always visible

0 ... 7

[ 0 ]

In addition to the manual error acknowledgement, an automatic one can also be selected.

0 = Off

1 ... 5 = Number of permissible automatic malfunction acknowledgments within one mains-on cycle.

After mains off and switch on again, the full amount is again available.

6 = Always, an error message will always be automatically acknowledged when the cause is no

longer present.

7 = ENTER key, acknowledgement is only possible using the ENTER key or by mains switch-off. No

acknowledgement is implemented by removing the enable!

P507

PPO type

always visible

1 ... 4

[ 1 ]

Only with the Profibus option

See also the additional description for the Profibus control - BU 0020 -

P508

Profibus address

always visible

1 ... 126

[ 1 ]

Profibus address, only with the Profibus option

See also the additional description for the Profibus control