3.2 Customer units

(Customer Units, Option)

Customer units are optional push-in modules whose slots are
located inside the frequency inverter. Following insertion and
switching on the mains supply, they are automatically identified
by the inverter, and the required parameters are made available.

Cable connection is via direct plug-in clip connectors with spring
terminals. This makes the connection of devices very easy and
convenient.

Customer unit

SK CU1-...

Description

Data

Basic I/O

SK CU1-BSC

Simplest custom interface for optimum adaptation to the

application.

1 x multifunction relays

3 x digital inputs

1 x analog input, 0...10V

Standard I/O

SK CU1-STD

Upgraded functionality of control signals, including USS

bus control.

2 x multifunction relays

4 x digital inputs

1 x analog input, 0...10V,

0/4...20mA

1 x analog outputs, 0...10V

1 x RS 485

Multi I/O

SK CU1-MLT

Top functionality of digital and analog signal processing.

2 x multifunction relays

6 x digital inputs

2 x analog inputs, -10...+10V,

0/4...20mA

2 x analog outputs, 0...10V

Multi I/O

SK CU1-MLT-20mA

Top functionality of digital and analog signal processing.

2 x multifunction relays

6 x digital inputs

2 x analog inputs, -10...+10V,

0/4...20mA

2 x analog outputs, 0/4...20mA

Profibus

SK CU1-PBR

This interface enables control of the NORDAC SK 700E

via the Profibus DP serial port.

1 x multifunction relays

1 x digital inputs

1 x Profibus

CAN bus

SK CU1-CAN-RJ

This unit enables control of the NORDAC SK 700E via

the CANbus port.

1 x multifunction relays

5 x digital inputs

2 x CANbus connectors RJ45

NOTE

,

for 5V / 15V power supplies

The customer units and special extension units currently have various power supplies (5V / 15V) that can
be used externally. The maximum permissible external load current is 300mA. This can be taken from
one or more power supplies. The total current must however not exceed 300mA.
All control voltages are based on a common reference potential!

Potentials AGND /0V und GND /0V are internally linked in the device.

Advertising