L2 l1 b2 t, 4 chassis line filter (accessory) – NORD Drivesystems BU0700 User Manual

Page 11

Advertising
background image

2 Assembly and installation

BU 0700 GB-1411

Subject to technical alterations

11

2.4 Chassis line filter (accessory)

In contrast to the line filter described in Chapter 2.3, the HLD 110 (up
to 110kW) has a UL acceptance for the North American market.

The interference noise suppression level of class A is achieved with
up to a maximum motor cable length of 50m, and class B with motor
cables of up to 25m.

When connecting the line filter, comply with Chapter 2.9 "Wiring
guidelines" and 8.3 "EMC". In particular, ensure that the pulse
frequency is set to the default value (P504 = 4/6kHz). The line filter
should be placed as close to the side of the inverter as possible.

The connection is by means of screw connections on the upper
(mains) and lower (inverter) ends of the filter

Inverter type

SK 700E ...

Filter type

HLD 110 - ...

[V] / [A]

Length

L1

Width

B1

Depth

T

Detail: mounting

Connection

cross-section

Length L2

Width B2

...-151-340-A
...-221-340-A

… 500/8

190

45

75

180

20

4 mm

2

...-301-340-A
...-401-340-A
...-551-340-A

… 500/16

250

45

75

240

20

4 mm

2

...-751-340-A
...-112-340-A

… 500/30

270

55

95

255

30

10 mm

2

...-152-340-A

… 500/42

310

55

95

295

30

10 mm

2

...-182-340-A

… 500/55

250

85

95

235

60

16 mm

2

...-222-340-A

...-302-340-O

… 500/75

270

85

135

255

60

35 mm

2

...-372-340-O

… 500/100

270

95

150

255

65

50 mm

2

...-452-340-O
...-552-340-O

… 500/130

...-752-340-O

… 500/180

380

130

181

365

102

95 mm

2

...-902-340-O
...-113-340-O

… 500/250

450

155

220

435

125

150 mm

2

Design variant, without UL, only noise suppression level A

Bus bar

...-133-340-O

HFD 103-500/300 *

564

300

160

2 x 210

275

8.5mm

...-163-340-O

HFD 103-500/400 *

10.5mm

*) without UL/cUL

All dimensions in mm

L1

L2

L3

L3'

L2'

L1'

L2

L1

B2

T

Netz / LINE

Gerät / LO

AD

B1

Advertising