Rated data, Operation at 400 v, Technical data – Lenze 9300 0.37kW-75kW User Manual

Page 130: Rated data operation at 400 v, 3 rated data

Advertising
background image

Technical data

Rated data
Operation at 400 V

3

l

130

EDKVS9332X DE/EN/FR 6.1

3.3

Rated data

)

Note!

The controllers EVS9324, EVS9326 and EVS9328 … EVS9332 may only be
operated with the prescribed mains chokes and mains filters.

3.3.1

Operation at 400 V

Basis of the data

Voltage

Frequency

AC mains connection

[V

rate

d

]

3/PE AC 320 V − 0 % ... 440 V + 0 %

45 Hz − 0 % ... 65 Hz + 0 %

DC−mains connection
(alternatively)

[U

DC

]

DC 450 V − 0 % ... 620 V + 0 %

˘

Output voltage

With mains choke

3 ~ 0 approx. 94 % V

rated

˘

Without mains choke

3 ~ 0 ... U

N

˘

9300

Mains current

1)

Typical motor power

Output power

Power loss

With

mains choke

Without

mains choke

ASM

(4−pole)

8 kHz

2)

U, V, W

+U

G

, −U

G

3)

Type

I

r

[A]

I

r

[A]

P

r

[kW]

P

r

[hp]

S

r8

[kVA]

P

DC

[kW]

P

V

[W]

EVS9321−xx

1.5

2.1

0.37

0.5

1.0

2.0

100

EVS9322−xx

2.5

3.5

0.75

1.0

1.7

0.75

110

EVS9323−xx

3.9

5.5

1.5

2.0

2.7

2.2

140

EVS9324−xx

7.0

˘

3.0

4.0

4.8

0.75

200

EVS9325−xx

12.0

16.8

5.5

7.5

9.0

0

260

EVS9326−xx

20.5

˘

11.0

15.0

16.3

0

390

EVS9327−xx

27.0

43.5

15.0

20.0

22.2

10

430

EVS9328−xx

44.0

˘

22.0

30.0

32.6

4

640

EVS9329−xx

53.0

˘

30.0

40.0

40.9

0

810

EVS9330−xx

78.0

˘

45.0

60.0

61.6

5

1100

EVS9331−xx

100

˘

55.0

75.0

76.2

0

1470

EVS9332−xx

135

˘

75.0

100

100.5

0

1960

Bold print = Lenze setting

1)

Mains currents at 8 kHz switching frequency

2)

Switching frequency of the inverter

3)

Power which can additionally be drawn from the DC bus at operation with power−adapted motor

Advertising