Mains choke/mains filter assignment, Electrical installation, Installation to ul – Lenze 9300 0.37kW-75kW User Manual
Page 161: 4 mains choke/mains filter assignment
![background image](/manuals/566007/161/background.png)
Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Mains choke/mains filter assignment
l
161
EDKVS9332X DE/EN/FR 6.1
Installation to UL
Supply conditions
Range
Description
Fuses
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
rms
: All classes are permissible
l
System short−circuit current up to 50000 A
rms
: Only classes "CC", "J", "T" or "R" permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation without mains choke/mains filter
EVS9321−xx
6
18
EVS9322−xx
6
18
EVS9323−xx
10
16
EVS9325−xx
25
10
Operation with mains choke/mains filter
EVS9321−xx
6
18
EVS9322−xx
6
18
EVS9323−xx
10
16
EVS9324−xx
10
16
EVS9325−xx
25
10
EVS9326−xx
25
10
Max. connection cross−section of the terminal strip: AWG 12, with pin−end connector AWG 10
5.4.4
Mains choke/mains filter assignment
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVS9321−xx
EZN3A2400H002
EZN3A2400H002
5
EZN3B2400H002
50
EVS9322−xx
EZN3A1500H003
EZN3A1500H003
5
EZN3B1500H003
50
EVS9323−xx
EZN3A0900H004
EZN3A0900H004
5
EZN3B0900H004
50
EVS9324−xx
EZN3A0500H007
EZN3A0500H007
5
EZN3B0500H007
50
EVS9325−xx
EZN3A0300H013
EZN3A0300H013
5
EZN3B0300H013
50
EVS9326−xx
ELN3−0150H024−001
EZN3A0150H024
5
EZN3B0150H024
50