Electrical installation, Motor with kty thermal sensor, We recommend to use lenze system cables for wiring – Lenze 9300 0.37kW-75kW User Manual
Page 173
![background image](/manuals/566007/173/background.png)
Electrical installation
Standard devices in the power range 15 ... 30 kW
Motor connection
l
173
EDKVS9332X DE/EN/FR 6.1
Characteristics of the connection for motor temperature monitoring:
Terminals T1, T2
Connection
l
PTC thermistor
– PTC thermistor with defined tripping temperature (acc. to DIN 44081 and
DIN 44082)
l
Thermal contact (NC contact)
– Thermostat as NC contact
Tripping point
l
Fixed (depending on the PTC/thermal contact)
l
PTC: R
J
>
1600
W
l
Configurable as warning or error (TRIP)
Notes
l
Monitoring is not active in the Lenze setting.
l
If you do not use a Lenze motor, we recommend the use of a PTC thermistor up
to 150°C.
PE
PE
T1
T1
T2
T2
U
V
W
4
4
T1
T2
2.5 Nm
22,1 lb-in
T1
T2
2.5 Nm
22,1 lb-in
}
+
PE
}
+
PE
0
0
1
1
3
2
2
U, V, W,
PE
5 Nm
44 lb-in
M 6
9300std030
Fig. 5−12
Motor connection with PTC thermistor or thermal contact (NC contact)
0 Motor connection with Lenze system cable with integrated control cable for the motor
temperature monitoring
1 Shield sheet
Clamp entire shield and shield of the control cable for the motor temperature monitoring
with the straps. If required, fix by means of cable tie.
0 Motor cable connection and separate control cable for the motor temperature monitoring
1 Shield sheet
Clamp shield of the motor cable and shield of the cable for the motor temperature
monitoring with the straps. If required, fix by means of cable tie.
2 PE stud
PE cable connection with ring cable lug
3 U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 50 mm
2
with ring cable lug
4 T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)
Motor with KTY thermal sensor
)
Note!
ƒ
We recommend to use Lenze system cables for wiring.
ƒ
For self−made cables only use cables with shielded cores twisted in pairs.