Electrical installation, Motor with kty thermal sensor, We recommend to use lenze system cables for wiring – Lenze 9300 0.37kW-75kW User Manual

Page 173

Advertising
background image

Electrical installation

Standard devices in the power range 15 ... 30 kW

Motor connection

5

l

173

EDKVS9332X DE/EN/FR 6.1

Characteristics of the connection for motor temperature monitoring:

Terminals T1, T2

Connection

l

PTC thermistor
– PTC thermistor with defined tripping temperature (acc. to DIN 44081 and

DIN 44082)

l

Thermal contact (NC contact)
– Thermostat as NC contact

Tripping point

l

Fixed (depending on the PTC/thermal contact)

l

PTC: R

J

>

1600

W

l

Configurable as warning or error (TRIP)

Notes

l

Monitoring is not active in the Lenze setting.

l

If you do not use a Lenze motor, we recommend the use of a PTC thermistor up
to 150°C.

PE

PE

T1

T1

T2

T2

U

V

W

4

4

T1
T2

2.5 Nm
22,1 lb-in

T1
T2

2.5 Nm
22,1 lb-in

}

+

PE

}

+

PE

0

0

1

1

3

2

2



‚

U, V, W,
PE

5 Nm
44 lb-in

M 6

9300std030

Fig. 5−12

Motor connection with PTC thermistor or thermal contact (NC contact)

 0 Motor connection with Lenze system cable with integrated control cable for the motor

temperature monitoring

1 Shield sheet

Clamp entire shield and shield of the control cable for the motor temperature monitoring
with the straps. If required, fix by means of cable tie.

‚ 0 Motor cable connection and separate control cable for the motor temperature monitoring

1 Shield sheet

Clamp shield of the motor cable and shield of the cable for the motor temperature
monitoring with the straps. If required, fix by means of cable tie.

2 PE stud

PE cable connection with ring cable lug

3 U, V, W

Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 50 mm

2

with ring cable lug

4 T1, T2 for motor temperature monitoring

Cable connection for PTC thermistors or thermal contacts (NC contacts)

Motor with KTY thermal sensor

)

Note!

ƒ

We recommend to use Lenze system cables for wiring.

ƒ

For self−made cables only use cables with shielded cores twisted in pairs.