State bus, Electrical installation, Stop – Lenze 9300 0.37kW-75kW User Manual
Page 198: Wiring of the control connections state bus, 4 state bus
Advertising
![background image](/manuals/566007/198/background.png)
Electrical installation
Wiring of the control connections
State bus
l
198
EDKVS9332X DE/EN/FR 6.1
5.8.4
State bus
(
Stop!
Destruction of the control card!
External voltage at X5/ST1, X5/ST2 destroys the control card.
Protective measure:
Do not connect an external voltage to X5/ST1, X5/ST2.
GND2
GND2
GND2
+24V
+24V
+24V
A2
A2
A2
A3
A3
A3
A4
A4
A4
ST1
ST1
ST1
ST2
ST2
ST2
59
59
59
39
39
39
47k
47k
47k
50mA
50mA
50mA
50mA
50mA
50mA
50mA
50mA
50mA
50mA
50mA
50mA
X5
X5
X5
A1
A1
A1
PES
PES
PES
PES
PES
9300std222
Fig. 5−30
Example for wiring a drive system to the STATE BUS
PES
HF shield termination by large−surface connection to PE