Mechanical installation – Lenze 9300 0.37kW-75kW User Manual

Page 139

Advertising
background image

Mechanical installation

Standard devices in the power range 0.37 ... 11 kW

Mounting in "cold plate" technique

4

l

139

EDKVS9332X DE/EN/FR 6.1

Dimensions

a

c1

c

c
a

a

c

g

g

g

b1

b1

b1

d

d

d

b

b

b

L

L

L

2

1

0

e

< 75 °C

3

9300std064

Fig. 4−3

Dimensions for mounting in "cold plate" technique 0.37 ... 11 kW

9300

Dimensions [mm]

Type

a

b

b1

c

c1

d

e

1)

g

EVS9321−Cx
EVS9322−Cx

0

78

381

350

48

˘

367

168

6.5

EVS9323−Cx
EVS9324−Cx

1

97

381

350

67

˘

367

168

6.5

EVS9325−Cx
EVS9326−Cx

2

135

381

350

105

38

367

168

6.5

1)

For a fieldbus module plugged onto X1, consider mounting space for connecting cables

Mounting

Apply heat conducting paste before screwing together the cooler and cooling plate of the
drive controller so that the heat transfer resistance is as low as possible.

1. Fasten the fixing bracket with sheet metal screws 3.5 × 13 mm at the top and

bottom of the drive controller

3.

2. Clean the contact surface of cooler and cooling plate with spirit.

3. Apply a thin coat of heat conducting paste with a filling knife or brush.

– The heat conducting paste in the accessory kit is sufficient for an area of approx.

1000 cm

2

.

4. Mount the drive controller on the cooler.