Electrical installation

Standard devices in the power range 0.37 ... 11 kW
Motor connection

5

l

162

EDKVS9332X DE/EN/FR 6.1

5.4.5

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor temperature
monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal contact

(NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for connecting a

KTY thermal sensor.

Shield sheet installation

(

Stop!

ƒ

To avoid damaging the PE stud, always install the shield sheet and the PE
connection in the order displayed. The required parts are included in the
accessory kit.

ƒ

Do not use lugs as strain relief.

PE

U V W

T1T2

M6

M5

a

1.7 Nm
15 lb-in

PE

M5
3.4 Nm
30 lb-in

}

+

PE

a

2 3

4 5

6 7

1

0

2

4

7

8

0

9300vec128

Fig. 5−4

Installation of shield sheet for drive controllers 0.37 ... 11 kW

0 PE stud

1 Screw on M5 nut and tighten hand−tight

2 Slide on fixing bracket for shield sheet

3 Slide on serrated lock washer

4 Slide on PE cable with ring cable lug

5 Slide on washer

6 Slide on spring washer

7 Screw on M5 nut and tighten it

8 Screw shield sheet on fixing bracket with two M4 screws (a)