Mains choke/mains filter assignment, Electrical installation – Lenze 9300 0.37kW-75kW User Manual
Page 179
![background image](/manuals/566007/179/background.png)
Electrical installation
Standard devices with a power of 45 kW
Mains choke/mains filter assignment
l
179
EDKVS9332X DE/EN/FR 6.1
Installation to UL
Supply conditions
Range
Description
Fuses
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
rms
: All classes permissible
l
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R" permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation with mains choke/mains filter
EVS9330−xx
100
1
5.6.4
Mains choke/mains filter assignment
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVS9330−xx
ELN3−0038H085
EZN3A0030H110
25
EZN3B0030H110
50
EZN3A0030H110N001
3)
25
E82ZN55334B230
50
3)
For controllers with thermal separation