Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Motor connection
l
166
EDKVS9332X DE/EN/FR 6.1
PE
U V W
T1T2
U, V, W
T1, T2
0.5...0.6 Nm
4.4...5.3 lb-in
2
1
0
9300vec122
Fig. 5−8
Motor connection with KTY thermal sensor
0 Motor cable
1 Shield sheet
Clamp the motor cable shield with the straps. If required, fix by means of cable tie.
2 U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable. Use wire end ferrules
for flexible cables.
Max. connectable cable cross−section: 4 mm
2
, with pin−end connector > 4 mm
2