Electrical installation, Stop – Lenze 9300 0.37kW-75kW User Manual

Page 193

Advertising
background image

Electrical installation

Wiring of the control connections

Important notes

5

l

193

EDKVS9332X DE/EN/FR 6.1

Terminal data

(

Stop!

ƒ

Connect or disconnect the terminal strips only if the controller is
disconnected from the mains!

ƒ

Wire the terminal strips before connecting them!

ƒ

Unused terminal strips must also be plugged on to protect the contacts.

Cable type

Wire end ferrule

Maximum cable
cross−section

Tightening torque Stripping

length

Rigid

2.5 mm

2

(AWG 14)

0.5 ... 0.6 Nm

(4.4 ... 5.3 lb−in)

5 mm

Flexible

Without wire end
ferrule

2.5 mm

2

(AWG 14)

Flexible

Wire end ferrule
without plastic sleeve

2.5 mm

2

(AWG 14)

Flexible

Wire end ferrule with
plastic sleeve

2.5 mm

2

(AWG 14)