Mechanical installation

Standard devices in the power range 15 ... 30 kW

Mounting in "cold plate" technique

4

l

143

EDKVS9332X DE/EN/FR 6.1

4.2.4

Mounting in "cold plate" technique

The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on collective coolers.
For this purpose, the drive controllers of type EVS93xx−Cxx must be used.

Requirements for collective coolers

The following points are important for safe and reliable operation of the controller:

ƒ

Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at

least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all

specified screw connections.

ƒ

Observe the thermal resistance R

th

given in the table. The values are valid for

controller operation under rated conditions.

9300

Cooling path

Power to be dissipated

Heatsink − environment

Type

P

v

[W]

R

th

[K/W]

EVS9327−Cx

410

0.085

EVS9328−Cx

610

0.057

Ambient conditions

ƒ

The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.

ƒ

Temperature at the cooling plate of the drive controller: max. 75 °C.